New Zealand Fiber Optic Supplier

You are here Transceivers MMC-16 APC to 2 x MTP-8 UPC Breakout

MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4

MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4

New Zealand engineering teams can use the documented values below to compare the product with the intended channel and as-built requirements. The 16FMMCMTPOM4 APC-to-UPC breakout divides sixteen OM4 fibers from one MMC APC female connector into two MTP-8 UPC female branches. It is built for multimode channels that require this particular polish combination. The direct fan-out replaces cassette-based conversion with one factory-tested item and two in clear terms identifiable eight-fiber optical routes.

Product Highlights

  • MMC Female to MTP® Female, 16 Fibers
  • OM4 50/125μm, bend-insensitive fiber
  • MMC insertion loss ≤0.35dB, return loss ≥40/27dB (MMC/MTP®)
  • Harness Polarity wiring scheme
  • 2.5mm Plenum (OFNP) cable
  • Standard length options: 1m (3ft), 2m (7ft), 3m (10ft)

Specifications

Part Number16FMMCMTPOM4
ManufacturerHT
Connector AUS Conec MMC Female (Non-Pinned)
Connector BUS Conec MTP® Elite Female (Non-Pinned)
Polish TypeAPC to UPC
Glass FiberBend Insensitive Fiber
Fiber ModeOM4 50/125μm
Wavelength850/1300nm
Fiber Count16 Fibers
PolarityHarness Polarity
Cable Outside Diameter (OD)2.5mm
Cable JacketPlenum (OFNP)
Min. Bend Radius (Optical Fiber)7.5mm
Min. Bend Radius (Fiber Cable)20/10D (Dynamic/Static)
Tensile Strength (Long Term)30N
Tensile Strength (Short Term)100N
Insertion Loss≤0.35dB
Return Loss≥40/27dB (MMC/MTP®)
Attenuation at 850nm≤2.3dB/km
Attenuation at 1300nm≤0.6dB/km
Operating Temperature-10 to 60°C (14 to 140℉)
Storage Temperature-10 to 70°C (14 to 158℉)

A mixed-polish multimode fan-out

APC at the MMC connection end and UPC at the two MTP ends must be compatible with the surrounding interfaces; this design ought to not be substituted for the APC-to-APC breakout. The female, non-pinned connectors require pinned mates. Because the two MTP branches may serve separate destination ports, label each separate branch and record its allocation before dressing the relevant cable into a manager.

Reflection and insertion-loss values by connector

Maximum insertion loss is 0.35dB. Return loss is specified separately as at least 40dB for the MMC APC interface and 27dB for the MTP UPC interface. Those figures should be retained in acceptance documentation rather than replaced by a single standard specification. OM4 fiber supports the 850/1300nm multimode optical path; at the same time, reach remains determined by the selected transceivers.

Installing the two-leg assembly

The standard full lengths are 1m (3ft), 2m (7ft) and 3m (10ft); project-specific meter and foot lengths are offered. Mounting point the relevant fan-out so neither MTP leg is pulled sideways, and respect the 7.5mm optical-fiber bend radius. Clean and review the MMC and the two MTP ferrules before making the three connections.

Ordering and Factory Support

Record 16FMMCMTPOM4 in the APC-to-UPC two-branch configuration, with length and quantity. For repeat installations, project-specific branch IDs and a customer part-number label may keep these mixed-polish cables distinct from the APC-to-APC variants. New Zealand project orders can include documentation and labeling requirements alongside the technical configuration.

New Zealand Fiber Optics

New Zealand Fiber Optics

New Zealand Service center: New Zealand 0632, Auckland.

Factory in Asia: Shangxue Industrial Area, Shenzhen

Product Datasheets

For PDF documents of products data sheet or any general inquiry, email info@huihongfiber.com and we will send you the details.

Customer Support

For customer support, please email sales@huihongfiber.com; our Auckland service team will respond promptly.